Common symptoms and corrective actions, Common symptoms and corrective actions -8 – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 90

Advertising
background image

4-8

Troubleshooting

Table 4.D Alarm Cross Reference – by Number

Common Symptoms and
Corrective Actions

Drive does not Start from Start or Run Inputs wired to the terminal block.

Drive does not Start from HIM.

VHz Neg Slope

24

[Torq Perf Mode] = “Custom V/Hz” & the V/Hz slope is negative.

Waking

11

The Wake timer is counting toward a value that will start the drive.

(1)

See

page 4-1

for a description of alarm types.

No.

(1)

(1)

Alarm numbers not listed are reserved for future use.

Alarm

No.

(1)

Alarm

No.

(1)

Alarm

1

Precharge Active

10

Decel Inhibt

23

MaxFreq Conflict

2

UnderVoltage

11

Waking

24

VHz Neg Slope

3

Power Loss

17

Dig In ConflictA

25

IR Volts Range

4

Start At PowerUp

18

Dig In ConflictB

26

FluxAmpsRef Rang

5

Analog in Loss

19

Dig In ConflictC

27

Speed Ref Cflct

6

IntDBRes OvrHeat

20

Bipolar Conflict

28

Ixo Vlt Rang

8

Drive OL Level 1

21

Motor Type Cflct

29

Sleep Config

9

Drive OL Level 2

22

NP Hz Conflict

Table 4.C Alarm Descriptions and Actions (Continued)

Alarm

No. Type

(1)

Description

Cause(s)

Indication

Corrective Action

Drive is faulted.

Flashing red
status light

Clear fault.

• Press Stop

• Cycle power

• Set [Fault Clear] to 1

(See page 3-23)

• “Clear Faults” on the HIM Diagnostic menu.

Incorrect input wiring. See pages

1-27

and

1-28

for wiring examples.

• 2 wire control requires Run, Run

Forward, Run Reverse or Jog input.

• 3 wire control requires Start and Stop

inputs.

• Jumper from terminal 25 to 26 is

required.

None

Wire inputs correctly and/or install jumper.

Incorrect digital input programming.

• Mutually exclusive choices have

been made (i.e., Jog and Jog
Forward).

• 2 wire and 3 wire programming may

be conflicting.

• Exclusive functions (i.e, direction

control) may have multiple inputs
configured.

• Stop is factory default and is not

wired.

None

Program [Digital Inx Sel] for correct inputs.

(See page 3-30)

Start or Run programming may be missing.

Flashing yellow
status light and
“DigIn CflctB”
indication on
LCD HIM.

[Drive Status 2]
shows type 2
alarm(s).

Program [Digital Inx Sel] to resolve conflicts.

(See page 3-30)

Remove multiple selections for the same
function.

Install stop button to apply a signal at stop
terminal.

Cause(s)

Indication

Corrective Action

Drive is programmed for 2 wire
control. HIM Start button is disabled
for 2 wire control.

None

If 2 wire control is required, no action needed.

If 3 wire control is required, program [Digital
Inx Sel] for correct inputs.

(See page 3-30)