Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 113

Advertising
background image

Application Notes

D-3

[Motor OL Hertz] defines the frequency where motor overload capacity
derate should begin. The motor overload capacity is reduced when
operating below [Motor OL Hertz]. For all settings of [Motor OL Hertz]
other than zero, the overload capacity is reduced to 70% at an output
frequency of zero.

[Motor NP FLA] is multiplied by [Motor OL Factor] to select the rated current
for the motor thermal overload. This can be used to raise or lower the level of
current that will cause the motor thermal overload to trip. The effective overload
factor is a combination of [Motor OL Hertz] and [Motor OL Factor].

Motor Overload Curve

100

125

150

175

200

225

250

Full Load Amps (%)

Tr

ip Time

(Sec)

Cold
Hot

10

100

1000

10000

100000

Changing Overload Hz

0

10

20

30

40

50

60

70

80

90 100

% of Base Speed

Contin

uous Rating

OL Hz = 10
OL Hz = 25
OL Hz = 50

0

20

40

60

80

100

120

Changing Overload Factor

0

10

20

30

40

50

60

70

80

90 100

% of Base Speed

Contin

uous Rating

OL % = 1.20
OL % = 1.00
OL % = 0.80

0

20

40

60

80

100

120

140