Programming and Parameters

3-23

UTI

L

ITY

Di

agnostic

s

229

[Alarm 1 @ Fault]

Captures and displays [Drive Alarm 1] at the time of the last fault.

Read Only

211

,

224

thru

230

230

[Alarm 2 @ Fault]

Captures and displays [Drive Alarm 2] at the time of the last fault.

Read Only

212

,

224

thru

230

234
236

[Testpoint 1 Sel]
[Testpoint 2 Sel]

Selects the function whose value is displayed value in [Testpoint x Data].

These are internal values that are not accessible through parameters.

See

Testpoint Codes and Functions on page 4-10

for a listing of available

codes and functions.

Default:

Min/Max:
Units:

499

0/65535
1

235
237

[Testpoint 1 Data]
[Testpoint 2 Data]

The present value of the function selected in [Testpoint x Sel].

Default:

Min/Max:
Units:

Read Only

0/4294967295
1

Fa

u

lt

s

238

[Fault Config 1]

Enables/disables annunciation of the listed faults.

240

[Fault Clear]

Resets a fault and clears the fault queue.

Default:

Options:

0

0
1
2

“Ready”

“Ready”
“Clear Faults”
“Clr Flt Que”

241

[Fault Clear Mode]

Enables/disables a fault reset (clear faults) attempt from any source. This
does not apply to fault codes which are cleared indirectly via other
actions.

Default:

Options:

1

0
1

“Enabled”

“Disabled”
“Enabled”

242

[Power Up Marker]

Elapsed hours since initial drive power up. This value will rollover to 0
after the drive has been powered on for more than the max value shown.
For relevance to most recent power up, see [Fault x Time].

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295 Hr
0.0001 Hr

244

,

246

,

248

,

250

,

252

,

254

,

256

,

258

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

0

0

0

0

0

0

x

0

0

0

0

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Condition True
0 =Condition False
x =Reserved

Bit #

Prec

hr

g Actv

UnderV

olta

ge

Po

wer Loss

Str At PwrUp

Anlg in Loss

IntDBRes OH

Dr

v OL Lvl 1

Dr

v OL Lvl 2

Decel Inhibt

W

aking

0

0

0

0

0

0

0

0

0

0

0

0

0

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Condition True
0 =Condition False
x =Reserved

Bit #

DigIn CflctA

DigIn CflctB

DigIn CflctC

Bipolr Cflct

MtrT

yp Cflct

NP Hz Cflct

MaxFr

q Cflct

VHz NegSlope

IR Vlts

Rang

FlxAmps Rang

SpdRef Cflct

Ixo Vlt

Rang

Sleep Config

32

1

x

1

0

0

0

1

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Po

wer Loss

UnderV

olta

ge

Motor OverLd

Shear Pin