Programming and Parameters

3-11

SPEED COMMA

N

D

Spee

d Ref

erenc

e

090

[Speed Ref A Sel]

Selects the source of the speed reference to the drive unless [Speed Ref
B Sel] or [Preset Speed 1-7] is selected.

(1)

See

Figure 1.4 on page 1-8

for DPI Port 3 location.

Default:

Options:

2

1
2
3-8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

“Analog In 2”

“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Reserved”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”

(1)

“DPI Port 2”

(1)

“DPI Port 3”

(1)

“DPI Port 4”

(1)

“DPI Port 5”

(1)

002

091

thru

093

101

thru

107

117

thru

120

192

thru

194

213

272

273

320

361

thru

366

091

[Speed Ref A Hi]

Scales the upper value of the [Speed Ref A Sel] selection when the
source is an analog input.

Default:

Min/Max:
Units:

[Maximum Speed]

–/+[Maximum Speed]
0.1 Hz

082

092

[Speed Ref A Lo]

Scales the lower value of the [Speed Ref A Sel] selection when the
source is an analog input.

Default:

Min/Max:
Units:

0.0

–/+[Maximum Speed]
0.1 Hz

081

093

[Speed Ref B Sel]

See

[Speed Ref A Sel]

.

Default:

Options:

11

“Preset Spd1”

See

[Speed Ref A Sel]

090

094

[Speed Ref B Hi]

Scales the upper value of the [Speed Ref B Sel] selection when the
source is an analog input.

Default:

Min/Max:
Units:

[Maximum Speed]

–/+[Maximum Speed]
0.1 Hz

093

095

[Speed Ref B Lo]

Scales the lower value of the [Speed Ref B Sel] selection when the
source is an analog input.

Default:

Min/Max:
Units:

0.0

–/+[Maximum Speed]
0.1 Hz

090

,

093

096

[TB Man Ref Sel]

Sets the manual speed reference source when a digital input is
configured for “Auto/Manual.”

(1)

“Analog In 2” is not a valid selection if it was selected for any of the
following:

- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep-Wake Ref]

Default:

Options:

1

1
2
3-8
9

“Analog In 1”

“Analog In 1”
“Analog In 2”

(1)

“Reserved”
“MOP Level”

097

,

098

097

[TB Man Ref Hi]

Scales the upper value of the [TB Man Ref Sel] selection when the
source is an analog input.

Default:

Min/Max:
Units:

[Maximum Speed]

–/+[Maximum Speed]
0.1 Hz

096

098

[TB Man Ref Lo]

Scales the lower value of the [TB Man Ref Sel] selection when the source
is an analog input.

Default:

Min/Max:
Units:

0.0

–/+[Maximum Speed]
0.1 Hz

096

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related