Application Notes

D-7

The drive must be running for the PI loop to be enabled. The loop will be
disabled when the drive is ramping to a stop (unless “Stop Mode” is
configured in [PI Configuration]), jogging or the signal loss protection for
the analog input(s) is sensing a loss of signal.

If a digital input has been configured to “PI Enable,” two events are required
to enable the loop: the digital input must be closed AND bit 0 of the PI
Control parameter must be = 1.

If no digital input is configured to “PI Enable,” then only the Bit 0 = 1
condition must be met. If the bit is permanently set to a “1”, then the loop
will become enabled as soon as the drive goes into “run.”

PI Enabled

Spd Cmd

PI Output

PI Pre-load Value

PI Pre-load Value = 0

PI Pre-load Value > 0

Pre-load to Command Speed

PI Enabled

Spd Cmd

PI Output

Start at Spd Cmd

-100.0

-75.0

-50.0

-25.0

0.0

25.0

50.0

75.0

100.0

Normalized Feedback

Nor

maliz

ed SQR

T(F

eedbac

k)

-100.0

-75.0

-50.0

-25.0

0.0

25.0

50.0

75.0

100.0