Utility file, Utility file -19 – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 67

Advertising
background image

Programming and Parameters

3-19

Utility File

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

UTI

L

ITY

Direction Config

190

[Direction Mode]

Selects the method for changing drive direction.

Default:

Options:

0

0
1
2

“Unipolar”

“Unipolar”
“Bipolar”
“Reverse Dis”

320

thru

327

361

thru

366

HIM Ref Config

192

[Save HIM Ref]

Enables a feature to save the present frequency reference value issued by the HIM to Drive memory on power loss.
Value is restored to the HIM on power up.

193

[Man Ref Preload]

Enables/disables a feature to automatically load the present “Auto”
frequency reference value into the HIM when “Manual” is selected. Allows
smooth speed transition from “Auto” to “Manual.”

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

MOP Config

194

[Save MOP Ref]

Enables/disables the feature that saves the present MOP frequency reference at power down or at stop.

195

[MOP Rate]

Sets rate of change of the MOP reference in response to a digital input.

Default:

Min/Max:
Units:

1.0 Hz/s

0.2/[Maximum Freq]
0.1 Hz/s

Drive Memor

y

196

[Param Access Lvl]

Selects the parameter display level.
Basic = Reduced parameter set
Advanced = Full parameter set

Default:

Options:

0

0
1
2

“Basic”

“Basic”
“Advanced”
“Reserved”

197

[Reset To Defaults]

Resets parameters to factory defaults except [Language], [Param Access
Lvl], and [Voltage Class] (params. 196, 201, and 202).
• Option 1 resets parameters to factory defaults based on [Voltage

Class].

• Options 2 and 3 will reset parameters to factory defaults and set

[Voltage Class] to low or high voltage settings.

Default:

Options:

0

0
1
2
3

“Ready”

“Ready”
“Factory”
“Low Voltage”
“High Voltage”

041

thru

047

054

,

063

,

069

thru

072

082

,

148

,

158

198

[Load Frm Usr Set]

Loads a previously saved set of parameter values from a selected user
set location in drive nonvolatile memory to active drive memory.

Default:

Options:

0

0
1
2
3

“Ready”

“Ready”
“User Set 1”
“User Set 2”
“User Set 3”

199

199

[Save To User Set]

Saves the parameter values in active drive memory to a user set in drive
nonvolatile memory.

Default:

Options:

0

0
1
2
3

“Ready”

“Ready”
“User Set 1”
“User Set 2”
“User Set 3”

198

Mode

Direction Change

Unipolar

Drive Logic

Bipolar

Sign of Reference

Reverse Dis

Not Changeable

x

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Save at Power Down
0 =Do Not Save
x =Reserved

Bit #

Factory Default Bit Values

At P

owr Do

wn

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Save at Power Down
0 =Do Not Save
x =Reserved

Bit #

Factory Default Bit Values

At P

owr Do

wn

At Stop