Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 66

Advertising
background image

3-18

Programming and Parameters

D

Y

NA

MA

NIC CO

NTR

O

L

P

o

wer Los

s

184

[Power Loss Mode]

Sets the reaction to a loss of input power. Power loss is recognized when:
• DC bus voltage is < 73% of [DC Bus Memory] and [Power Loss Mode]

is set to “Coast.”

• DC bus voltage is < 82% of [DC Bus Memory] and [Power Loss Mode]

is set to “Decel.”

Default:

Options:

0

0
1
2
3
4

“Coast”

“Coast”
“Decel”
“Continue”
“Coast Input”
“Decel Input”

013

,

185

185

[Power Loss Time]

Sets the time that the drive will remain in power loss mode before a fault
is issued.

Default:

Min/Max:
Units:

0.5 Secs

0.0/60.0 Secs
0.1 Secs

184

186

[Power Loss Level]

Sets the level at which the [Power Loss Mode] selection will occur.

Default:

Min/Max:
Units:

Drive Rated Volts

0.0/999.9 VDC
0.1 VDC

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

The drive can use the percentages referenced in [Power Loss Mode] or a trigger point can be set for line loss
detection as follows:

V

trigger

= [DC Bus Memory] – [Power Loss Level]

A digital input (programmed to “29, Pwr Loss Lvl”) is used to toggle between fixed percentages and the detection
level.

!

ATTENTION: Drive damage can occur if proper input impedance is not provided as explained below.

If the value for [Power Loss Level] is greater than 18% of [DC Bus Memory], the user must provide a
minimum line impedance to limit inrush current when the power line recovers. The input impedance
should be equal to or greater than the equivalent of a 5% transformer with a VA rating 5 times the
drives input VA rating.