Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 57

Advertising
background image

Programming and Parameters

3-9

MO

T

O

R CO

NTR

O

L

Vo

lt

s p

er

H

er

tz

069

[Start/Acc Boost]

Sets the voltage boost level for starting and acceleration when “Custom
V/Hz” mode is selected. Refer to parameter 083 [Overspeed Limit].

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Motor NP Volts]

× 0.25

0.1 VAC

053

,

070

070

[Run Boost]

Sets the boost level for steady state or deceleration when “Fan/Pmp
V/Hz” or “Custom V/Hz” modes are selected. See parameter 083
[Overspeed Limit].

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Motor NP Volts]

× 0.25

0.1 VAC

053

,

069

071

[Break Voltage]

Sets the voltage the drive will output at [Break Frequency]. Refer to
parameter 083 [Overspeed Limit].

Default:

Min/Max:
Units:

[Motor NP Volts]

× 0.25

0.0/[Motor NP Volts]
0.1 VAC

053

,

072

072

[Break Frequency]

Sets the frequency the drive will output at [Break Voltage]. Refer to
parameter 083.

Default:

Min/Max:
Units:

[Motor NP Hz]

× 0.25

0.0/[Maximum Freq]
0.1 Hz

053

,

071

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

Advertising