Application Notes

D-13

Ramp to Stop

This method uses drive output reduction to stop the load.

1. On Stop, drive output will decrease according to the programmed pattern from its

present value to zero. The pattern may be linear or squared. The output will decrease
to zero at the rate determined by the programmed [Maximum Freq] and the
programmed active [Decel Time x].

2. The reduction in output can be limited by other drive factors such as such as bus or

current regulation.

3. When the output reaches zero the output is shut off.

4. The motor, if rotating, will coast from its present speed for a time that is dependent on

the mechanics of the system (inertia, friction, etc).

Ramp to Hold

This method combines two of the methods above. It uses drive output reduction to stop
the load and DC injection to hold the load at zero speed once it has stopped.

1. On Stop, drive output will decrease according to the programmed pattern from its

present value to zero. The pattern may be linear or squared. The output will decrease
to zero at the rate determined by the programmed [Maximum Freq] and the
programmed active [Decel Time x]

2. The reduction in output can be limited by other drive factors such as bus or current

regulation.

3. When the output reaches zero 3 phase drive output goes to zero (off) and the drive

outputs DC voltage on the last used phase at the level programmed in [DC Brake
Level] Par 158. This voltage causes a “holding” brake torque.

4. DC voltage to the motor continues until a Start command is reissued or the drive is

disabled.

5. If a Start command is reissued, DC Braking ceases and he drive returns to normal

AC operation. If an Enable command is removed, the drive enters a “not ready” state
until the enable is restored.

Mode

Description

DC Hold Time

DC

Hold

Level

Stop

Command

Time

Output Voltage

Output Current

Motor Speed

Output Voltage

Output Current

Zero

Command

Speed

DC

Hold Level

Time

Output Voltage

Output Voltage

Output Current

Output Current

Motor Speed

Output Voltage

Output Current

Motor Speed

Re-issuing a
Start Command

Stop

Command

Zero

Command

Speed