background image

3-26

Programming and Parameters

C

O

MMUNICA

TIO

N

Ma

sks &

Owner

s

283

[Fault Clr Mask]

Controls which adapters can clear a fault.

See

[Logic Mask]

.

288

thru

297

284

[MOP Mask]

Controls which adapters can issue MOP commands to the drive.

See

[Logic Mask]

.

288

thru

297

285

[Local Mask]

Controls which adapters are allowed to take exclusive control of drive
logic commands (except stop). Exclusive “local” control can only be taken
while the drive is stopped.

See

[Logic Mask]

.

288

thru

297

288

[Stop Owner]

Adapters that are presently issuing a valid stop command.

Read Only

276

thru

285

289

[Start Owner]

Adapters that are presently issuing a valid start command.

See

[Stop Owner]

.

276

thru

285

290

[Jog Owner]

Adapters that are presently issuing a valid jog command.

See

[Stop Owner]

.

276

thru

285

291

[Direction Owner]

Adapter that currently has exclusive control of direction changes.

See

[Stop Owner]

.

276

thru

285

292

[Reference Owner]

Adapter that has the exclusive control of the command frequency source
selection.

See

[Stop Owner]

.

276

thru

285

293

[Accel Owner]

Adapter that has exclusive control of selecting [Accel Time 1, 2].

See

[Stop Owner]

.

140

,

276

thru

285

294

[Decel Owner]

Adapter that has exclusive control of selecting [Decel Time 1, 2].

See

[Stop Owner]

.

142

,

276

thru

285

295

[Fault Clr Owner]

Adapter that is presently clearing a fault.

See

[Stop Owner]

.

276

thru

285

296

[MOP Owner]

Adapters that are currently issuing increases or decreases in MOP
command frequency.

See

[Stop Owner]

.

276

thru

285

297

[Local Owner]

Adapter that has requested exclusive control of all drive logic functions. If
an adapter is in local lockout, all other functions (except stop) on all other
adapters are locked out and non-functional. Local control can only be
obtained when the drive is not running.

See

[Stop Owner]

.

276

thru

285

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

0

0

0

1

0

0

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Issuing Command
0 =No Command
x =Reserved

Bit #

Digital In

DPI P

or

t 1

DPI P

or

t 2

DPI P

or

t 3

DPI P

or

t 4

DPI P

or

t 5

Advertising