B-4
Adapter Parameters
15
[DSI I/O Cfg]
Sets the configuration of the Drives that are active
in the Multi-Drive mode. Identifies the connections
that would be attempted on a reset or power cycle.
Default:
0001
Values:
0 = Drive 0
1 = Drives 0-1
2 = Drives 0-2
3 = Drives 0-3
4 = Drives 0-4
Type:
Read/Write
Reset Required:
Yes
16
[DSI I/O Act]
Displays the Drives that are active in the
Multi-Drive mode.
Default:
0001
Bit Values:
0 = Drive 0
1 = Drives 0-1
2 = Drives 0-2
3 = Drives 0-3
4 = Drives 0-4
Type:
Read Only
17
18
19
20
21
[Drv 0 Addr]
[Drv 1 Addr]
[Drv 2 Addr]
[Drv 3 Addr]
[Drv 4 Addr]
Sets the corresponding node addresses of the
daisy-chained drives when the adapter Mode
Jumper (J2) is set for Multi-Drive operation.
Important: The settings for these parameters
must match the Parameter A104 - [Comm Node
Addr] settings in the respective drives. Each
setting must also be unique (no duplicate node
address).
Default:
1
Default:
2
Default:
3
Default:
4
Default:
5
Minimum:
1
Maximum:
247
Type:
Read/Write
Reset Required:
Yes
Parameter
No. Name and Description
Details