Setting the node address, Setting the data rate – Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual

Page 31

Advertising
background image

Configuring the Adapter

3-7

The value of Parameter 02 - [DN Addr Cfg] determines the node
address if all of the adapter DIP switches are in the CLOSED position
(all 0’s). We recommend that you do not use node address 63 because all
new devices use it as the default address. Address 63 is also used for
Automatic Device Recovery (ADR).

1. Set the value of Parameter 02 - [DN Addr Cfg] to a unique node

address.

Figure 3.5 DeviceNet Node Address Screen on PowerFlex 4-Class HIM (22-HIM-*)

2. Reset the adapter. Refer to

Resetting the Adapter

section in this chapter.

The value of Parameter 04 - [DN Rate Cfg] determines the DeviceNet
data rate if all of the adapter DIP switches are in the CLOSED position
(all 0’s). The Autobaud setting will detect the data rate used on the
network if another device is setting the data rate. Your application may
require a different setting.

1. Set the value of Parameter 04 - [DN Rate Cfg] to the data rate at

which your network is operating.

Figure 3.6 DeviceNet Data Rate Screen on PowerFlex 4-Class HIM (22-HIM-*)

2. Reset the adapter. Refer to

Resetting the Adapter

section in this chapter.

Setting the Node Address

DN Addr Cfg

Parameter:

#

002

63

VALUE

LIMITS

SEL

!

Default = 63

TIP: If you are using RSNetWorx for DeviceNet, select Network >
Single Browse Path
to see the new address; then delete the old address.

Setting the Data Rate

Value Baud Rate
0

125 kbps

1

250 kbps

2

500 kbps

3

Autobaud (Default)

DN Rate Cfg

Parameter:

#

004

Autobaud

3

VALUE

LIMITS

SEL

!