Plc-5 example, Plc-5 example -7 – Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual
Page 51

Using I/O Messaging
5-7
Figure 5.4 Control File for Block Transfers
PLC-5 Example
EN ST DN ER CO EW NR TO RW RLEN DLEN FILE
ELEM R
G
S
BT20:0 0
0
0
0
0
0
0
0
0
62
0
9
0
00
0
0
BT20:1 0
0
0
0
0
0
0
0
0
62
0
10
0
00
0
0
Figure 5.5 Example PLC-5 Ladder Logic Program
PLC-5 example program with a PowerFlex 40 at DeviceNet node address 1.
The DeviceNet scanner gathers the drive status data via the network. The BTR in this rung
then moves the drive status data from the scanner to the N9: data file in the PLC, where:
N9:0 = Scanner Status word
N9:1 = PowerFlex 40 (node 1) Logic Status
N9:2 = PowerFlex 40 (node 1) Feedback
Note that the Feedback for the PowerFlex 40 is received in Hz and not in engineering units
like other PowerFlex drives. For example, "300" equates to 30.0 Hz (the decimal point is
always implied).
0000
BT20:0
EN
EN
DN
ER
BTR
Block Transfer Read
Module Type 1771-SDN DeviceNet Scanner Module
Rack
000
Group
0
Module
0
Control Block
BT20:0
Data File
N9:0
Length
62
Continuous
No
Setup Screen
BTR
This rung enables the DeviceNet scanner.
0001
N10:0
0
1771-SDN
Scanner
Enable bit