8-2

Troubleshooting

PORT Status Indicator

Status

Cause

Corrective Action

Off

The adapter is not powered or
is not connected properly to
the drive.

• Securely connect the adapter to the drive

using the ribbon cable.

• Apply power to the drive.

Flashing
Red

The adapter is not receiving
communication from the drive,
connected drive is faulted, or
a drive is missing in
Multi-Drive mode.

• Clear any drive faults.
• Verify that cables are securely connected.
• Cycle power to the drive.

Solid
Red

The drive has refused an
I/O connection from the
adapter.

Another DSI peripheral is
using the same DSI port as
the adapter.

Important: Cycle power to the product after
making the following correction:

Verify that all DSI cables are securely
connected and not damaged. Replace cables
if necessary.

Flashing
Green

The adapter is establishing an
I/O connection to the drive or
[DSI I/O Config] is configured
for all I/O disabled.

• No Action. This status indicator will turn

solid green or red.

• Verify Parameter 15, [DSI I/O Config]

settings.

• Normal behavior if no DSI I/O is enabled.

Solid
Green

The adapter is properly
connected and is
communicating with the drive.

No Action.

Orange

Daisy-chained drives in
Multi-Drive mode are not all
Allen-Bradley drives
(PowerFlex 4/40).

Use Allen-Bradley PowerFlex 4/40’s for the
daisy-chained drives.