8-4

Troubleshooting

The following diagnostic items can be accessed using DriveExplorer
(version 3.01 or higher).

Net A Status Indicator

Status

Cause

Corrective Actions

Off

The adapter and/or
network is not powered or
adapter is not connected
properly to the network.

• Securely connect the adapter to the drive

using the Internal Interface cable and to the
network using a DeviceNet cable.

• Correctly connect the DeviceNet cable to the

DeviceNet plug.

• Apply power to the drive and network.

Flashing
Red

A DeviceNet I/O
connection has timed out.

• Place the scanner in RUN mode, or apply

power to the peer device that will send I/O.

• Check the amount of traffic on the network.

Solid
Red

Failed duplicate node
detection test or bus off
condition exists.

• Configure the adapter to use a unique node

address on the DeviceNet network.

• Configure the adapter to use the correct

network data rate.

• Ensure network has correct media installed.

Flashing
Green

The adapter is properly
connected but is not
communicating with any
devices on the network.

• Place the controller in RUN mode, or apply

power to the peer device that will send I/O.

• Program a controller or peer device to

recognize and transmit I/O to the adapter.

• Configure the adapter for the program in the

controller or the I/O from the peer device.

Solid
Green

The adapter is properly
connected and
communicating on the
network.

No action required.

Module Diagnostic Items in Single Drive Mode

No.

Name

Description

1

Field Flash Cnt

The number of flash updates made to the adapter after shipping.

2

Adapter Events

The number of events in the event queue.

3

Reference

Reference being transmitted to the host by this peripheral.

4

Logic Cmd

Command being transmitted to the host by this peripheral.

5

Logic Sts

Status being received from the host by this peripheral.

6

Feedback

Feedback being received from the host by this peripheral.

7

DN Rx Errors

Current value of the DeviceNet CAN Receive Error Counter register.

8

DN Tx Errors

Current value of the DeviceNet CAN Transmit Error Counter register.

9

Data Rate SW

Current setting of the adapter 2-bit data rate switch.

10

Node Address SW Current setting of the adapter 6-bit Node address switch.