Using Multi-Drive Mode

7-5

The following parameters must be set in the daisy-chained drives:

Note that the RS-485 network is fixed at 19.2K baud, 8 data bits, no
parity, and 1 stop bit.

Important: Parameters A105 - [Comm Loss Action] and A106 -

[Comm Loss Time] in the daisy-chained drives are not
used in Multi-Drive mode. If the RS-485 cable is
disconnected or broken, the disconnected drive(s) will fault.
On the DeviceNet side, Parameters 07 - [Comm Flt
Action]
and 08 - [Idle Flt Action] in the 22-COMM-D
determine the action taken for ALL of the drives on the
Multi-Drive node.

The following Multi-Drive parameters must be set in the 22-COMM-D:

After setting the 22-COMM-D parameters, set the adapter Mode Jumper
from Single drive operation to Multi-Drive operation, and reset the
adapter or cycle power. Refer to

Chapter 2

,

Commissioning the Adapter

.

Important: 22-COMM-D parameters can be set using a DSI peripheral

(HIM, DriveExplorer with 22-SCM-232, etc.) ONLY when
the Mode Jumper is in the Single mode position.

Configuring the RS-485 Network

Parameter

Value

P36 - [Start Source]

5 (“RS485 [DSI] Port”)

P38 - [Speed Reference]

5 (“RS485 [DSI] Port”)

A103 - [Comm Data Rate]

4 (“19.2K”)

A104 - [Comm Node Addr]

1-247 (must be unique)

A107 - [Comm Format]

0 (“RTU 8-N-1”)

Parameter

Value

15 - [DSI I/O Cfg]

00010 = Drives 0-1 connected
00100 = Drives 0-2 connected
01000 = Drives 0-3 connected
10000 = Drives 0-4 connected

17 - [Drv 0 Addr]

= Parameter A104 - [Comm Node Address] in Drive 0

18 - [Drv 1 Addr]

= Parameter A104 - [Comm Node Address] in Drive 1

19 - [Drv 2 Addr]

= Parameter A104 - [Comm Node Address] in Drive 2

20 - [Drv 3 Addr]

= Parameter A104 - [Comm Node Address] in Drive 3

21 - [Drv 4 Addr]

= Parameter A104 - [Comm Node Address] in Drive 4