Mapping the output i/o – Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual
Page 42

4-6
Configuring the Scanner
If you selected the Automap on Add box in the Scanlist page (
), RSNetWorx has already mapped the I/O. If it is not mapped, click
Automap to map it. If you need to change the mapping, click Advanced
and change the settings.
2. In the Memory box, select a location in scanner memory.
In our example, we are using a 1747-SDN and selected Discrete.
3. In the Start Word box, select the word in memory at which the data
should start. In our example, Logic Status and Speed Feedback
information will be found in I:1.1 and I:1.2, respectively.
Mapping the Output I/O
1. In the Scanner Module dialog box, click the Output tab. To display
this dialog box, right-click the scanner in the configuration view
(
Figure 4.6 Output Page on the Scanner Module Dialog Box
Scanner
Memory Locations
1747-SDN
Discrete or M-File
1756-DNB
Assembly Data
1771-SDN
Block Xfer 62 – 57