Getting Started

1-5

This section is designed to help experienced users start using the
DeviceNet adapter. If you are unsure how to complete a step, refer to the
referenced chapter.

Quick Start

Step

Refer to

1

Review the safety precautions for the adapter.

Throughout This
Manual

2

Verify that the PowerFlex drive is properly installed.

Drive User
Manual

3

Commission the adapter.
Set a unique node address and the appropriate data rate using
the switches on the adapter. If desired, you can disable the
switches and use parameter settings instead.

Chapter 2

,

Installing the
Adapter

4

Install the adapter.
Verify that the PowerFlex drive and DeviceNet network are not
powered. Then, connect the adapter to the network using a
DeviceNet cable and to the drive using the Internal Interface
cable. Use the captive screws to secure and ground the adapter
to the drive.

5

Apply power to the adapter.
The adapter receives power from the drive and network. Apply
power to the network and to the drive. The status indicators
should be green. If they flash red, there is a problem. Refer to

Chapter 8

,

Troubleshooting

.

6

Configure the adapter for your application.
Set the following parameters for the adapter as required by your
application:
• Node address and data rate.

• I/O configuration.

• Change of State, Cyclic, or polled I/O data exchange.

• Fault actions.

Chapter 3

,

Configuring the
Adapter

7

Apply power to the DeviceNet master and other devices on
the network.
Verify that the master and network are installed and functioning in
accordance with DeviceNet standards, and then apply power to
them.

DeviceNet
Cable System
Planning and
Installation
Manual

8

Configure the scanner to communicate with the adapter.
Use a network tool such as RSNetWorx for DeviceNet to
configure the scanner on the network. Make sure to:
• Set up the scan list.

• Map the adapter data to the scan list.

• Save your DeviceNet configuration to the scanner and a file.

Chapter 4

,

Configuring the
Scanner

9

Create a ladder logic program.
Use a programming tool such as RSLogix to create a ladder logic
program that enables you to do the following:
• Control the adapter and connected drive.

• Monitor or configure the drive using Explicit Messages.

Chapter 5

,

Using I/O
Messaging

Chapter 6

,

Using Explicit
Messaging