3-12

Configuring the Adapter

The following parameters provide information about how the adapter is
configured. You can view these parameters at any time.

Viewing the Adapter Configuration

Number

Name

Description

01

Mode

The mode in which the adapter is set
(0 = Single drive operation, or 2 = Multi-Drive operation).

03

DN Addr
Actual

The node address used by the adapter. This will be one of the
following values:
• The address set by the adapter DIP switches 1 through 6.
• The value of Parameter 02 - [DN Addr Config] if the

switches have been disabled.

• An old address of the switches or parameter if they have

been changed and the adapter has not been reset.

05

DN Rate
Actual

The data rate used by the adapter. This will be one of the
following values:
• The data rate set by the adapter DIP switches 7 and 8.
• The value of Parameter 04 - [DN Rate Config] if the

switches have been disabled.

• An old data rate of the switches or parameter if they have

been changed and the adapter has not been reset.

09

DN Active
Config

The source from which the adapter node address and data
rate are taken. This will be either switches or parameters in
EEPROM. It is determined by the settings of the adapter DIP
switches 1 through 8.

16

DSI I/O
Actual

Indicating the Drives that make up the node:

Values
0 = Drive 0
1 = Drives 0-1
2 = Drives 0-2
3 = Drives 0-3
4 = Drives 0-4