Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual

Page 40

Advertising
background image

4-4

Configuring the Scanner

Figure 4.4 Edit I/O Parameters Dialog Box

8. Select the type(s) of data exchange (Polled, Change of State, and /or

Cyclic). In our example, we selected Polled.

9. Type the number of bytes that are required for your I/O in the Input

Size and Output Size boxes. The size will depend on the I/O that you
enabled in the adapter. This information can be found in Parameter
16 - [DSI I/O Actual]
in the adapter.

Table 4.A

shows common

configuration Input/Output sizes.

In our example, we typed 4 in the Input Size and Output Size boxes
because the Mode Jumper on the adapter is set to “Single” (default)
and Parameter 16 - [DSI I/O Active] is set to “Drive 0” (only one
drive being connected). Logic Command/Reference uses 4 bytes and
Logic Status/Feedback uses 4 bytes.

Table 4.A Input/Output Size Configurations

10. Set the scan rate.

Input
Size

Output
Size

Logic Command/
Status

Reference/
Feedback

Parameter 16 -
[DSI I/O Active]

Parameter 1 -
[Mode]

4

4

Drive 0

Single

8

8

Drives 0-1

Multi-Drive

12

12

Drives 0-2

16

16

Drives 0-3

20

20

Drives 0-4

Data Exchange

Rate to set

Polled

Polled Rate

Change of State

Heartbeat Rate

Cyclic

Send Rate