Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual
Page 40

4-4
Configuring the Scanner
Figure 4.4 Edit I/O Parameters Dialog Box
8. Select the type(s) of data exchange (Polled, Change of State, and /or
Cyclic). In our example, we selected Polled.
9. Type the number of bytes that are required for your I/O in the Input
Size and Output Size boxes. The size will depend on the I/O that you
enabled in the adapter. This information can be found in Parameter
16 - [DSI I/O Actual] in the adapter.
shows common
configuration Input/Output sizes.
In our example, we typed 4 in the Input Size and Output Size boxes
because the Mode Jumper on the adapter is set to “Single” (default)
and Parameter 16 - [DSI I/O Active] is set to “Drive 0” (only one
drive being connected). Logic Command/Reference uses 4 bytes and
Logic Status/Feedback uses 4 bytes.
Table 4.A Input/Output Size Configurations
10. Set the scan rate.
Input
Size
Output
Size
Logic Command/
Status
Reference/
Feedback
Parameter 16 -
[DSI I/O Active]
Parameter 1 -
[Mode]
4
4
✔
✔
Drive 0
Single
8
8
✔
✔
Drives 0-1
Multi-Drive
12
12
✔
✔
Drives 0-2
16
16
✔
✔
Drives 0-3
20
20
✔
✔
Drives 0-4
Data Exchange
Rate to set
Polled
Polled Rate
Change of State
Heartbeat Rate
Cyclic
Send Rate