Using Multi-Drive Mode

Drive 0 - Drive 4 Control Routines

The Drive Control routines provide status information (Logic Status and
Feedback), control (Logic Command and Reference), and parameter
read/write for each of the respective drives. See

Figure 7.7

for Drive 0,

Figure 7.8

for Drive 1,

Figure 7.9

for Drive 2,

Figure 7.10

for Drive 3,

and for Drive 4.

Figure 7.6 Main Routine (Continued)

This section writes the output image to the scanner. The output image is as follows:

DriveOutputImage[0] and DriveOutputImage[1] = Drive 0 Logic Command and Reference
DriveOutputImage[2] and DriveOutputImage[3] = Drive 1 Logic Command and Reference
DriveOutputImage[4] and DriveOutputImage[5] = Drive 2 Logic Command and Reference
DriveOutputImage[6] and DriveOutputImage[7] = Drive 3 Logic Command and Reference
DriveOutputImage[8] and DriveOutputImage[9] = Drive 4 Logic Command and Reference

(Note the length of the COP instruction is "5" because the Destination address is a DINT)

7

Copy File
Source DriveOutputImage[0]
Dest

Local:3:O.Data[0]

Length

5

COP

This section writes the output image to the scanner. The output image is as follows:

DriveOutputImage[0] and DriveOutputImage[1] = Drive 0 Logic Command and Reference
DriveOutputImage[2] and DriveOutputImage[3] = Drive 1 Logic Command and Reference
DriveOutputImage[4] and DriveOutputImage[5] = Drive 2 Logic Command and Reference
DriveOutputImage[6] and DriveOutputImage[7] = Dr e 3 Logic Command and Reference
DriveOutputImage[8] and DriveOutputImage[9] = Drive 4 Logic Command and Reference

(Note the length of the COP instruction is "5" because the Destination address is a DINT)