Register object – Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual

Page 115

Advertising
background image

DeviceNet Objects

C-7

Class Attributes

Not supported.

Instance Attributes

Important: Setting a register object attribute can only be accomplished

through a connection with a non-zero expected packet rate
(EPR). This feature is to prevent accidental control of a DSI
device.

Services

Register Object

(Continued)

Attribute
ID

Access Rule Name

Data Type

Description

1

Get

Bad Flag

BOOL

If set to 1, then attribute 4
may contain invalid, bad or
otherwise corrupt data.
0 = good
1 = bad

2

Get

Direction

BOOL

Direction of data transfer
0 = Producer Register
1 = Consumer Register

3

Get

Size

UINT

Size of register data in bits

4

Conditional

(1)

(1)

The access rule of Set is optional if attribute 2, Direction = 1. If Direction = 0, the
access rule is Get.

Data

ARRAY of
BITS

Data to be transferred

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single