Register object – Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual
Page 115
DeviceNet Objects
C-7
Class Attributes
Not supported.
Instance Attributes
Important: Setting a register object attribute can only be accomplished
through a connection with a non-zero expected packet rate
(EPR). This feature is to prevent accidental control of a DSI
device.
Services
Register Object
(Continued)
Attribute
ID
Access Rule Name
Data Type
Description
1
Get
Bad Flag
BOOL
If set to 1, then attribute 4
may contain invalid, bad or
otherwise corrupt data.
0 = good
1 = bad
2
Get
Direction
BOOL
Direction of data transfer
0 = Producer Register
1 = Consumer Register
3
Get
Size
UINT
Size of register data in bits
4
Conditional
(1)
(1)
The access rule of Set is optional if attribute 2, Direction = 1. If Direction = 0, the
access rule is Get.
Data
ARRAY of
BITS
Data to be transferred
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single