Current Limit Stop

Current Limit stop is not typically set up as the normal Stop mode. Usually the
normal stop is programmed at some ramp rate. For the current limit stop a digital
input is used for the function. However, you certainly could set the normal stop
as CurrentLimit Stop

Current limit stop ramp rate is 0.1 second and is not programmable

Example

In this example the current limit was set high enough to allow the full rating of
the drive to be used in the stop sequence.

Bus Voltage

Output Voltage

Output Current

Motor Speed

Current Limit

Time

Stop Command

Zero Speed

Current Limit Stop

DC Bus Voltage

Motor Current

P685

Motor Speed

DC Bus

Vo

ltage