Setpoint – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual
Page 118
Advertising
118
Rockwell Automation Publication 750-RM002B-EN-P - September 2013
Chapter 2
Feedback and I/O
Setpoint
Setpoint is a possible source for an analog output. It can be used to control an
analog output from a communication device using a DataLink. Change P75
[Anlg Out0 Sel] to 76 [Anlg Out0 Stpt]. Then map a datalink to P76 and you’ll
be able to drive the analog output over a network.