Pid status, Pid reference and feedback, Pid reference and feedback scaling – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 85

Advertising
background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

85

Drive Configuration

Chapter 1

PID Status

P1089 [PID Status] parameter is a set of bits that indicate the status of the
process PID controller.

PID Reference and Feedback

The selection of the source for the reference signal is entered in P1067 [PID Ref
Sel]. The selection of the source for the feedback signal is selected in P1072 [PID
Fdbk Sel]. The reference and feedback have the same limit of possible options.

Options include DPI adapter ports, MOP, preset speeds, analog inputs, pulse
input, encoder input and PID setpoint parameter.

The value used for reference is displayed in P1090 [PID Ref Meter] as a read only
parameter. The value used for feedback is displayed in P1091 [PID Fdbk Meter]
as a read only parameter. These displays are active independent of PID Enabled.
Full scale is displayed as ±100.00%.

PID Reference and Feedback Scaling

The analog PID reference can be limited by using P1068 [PID Ref AnlgHi] and
P1069 [PID Ref AnlgLo]. [PID Ref AnlgHi] determines the high value, in
percent, for the analog PID reference. [PID Ref AnlgLo] determines the low
value, in percent, for the PID reference.

The analog PID feedback can be limited by using P1068 [PID Ref AnlgHi] and
P1069 [PID Ref AnlgLo]. [PID Ref AnlgHi] determines the high value, in
percent, for the PID feedback. [PID Ref AnlgLo] determines the low value, in
percent, for the PID feedback.

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

APPLIC

AT

IONS

P

ro

ce

ss PID

1089

PID Status
PID Status

RO

16-bit
Integer

Status of the Process PI regulator.

Bit 0 “PID Enable” – PID controller is enabled.
Bit 1 “PID Hold” – Hold PID integrator.
Bit 2 “PID Reset” – Reset PID integrator.
Bit 3 “PID In Limit” – PID in limit.

Options

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

PI

D In Lim

it

PI

D Reset

PI

D Hol

d

PI

D Enabled

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True

Advertising
This manual is related to the following products: