Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 275

Advertising
background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

275

Motor Control

Chapter 4

With default parameter settings, this will occur when the speed error becomes
negative. When forced speed mode is off, the drive will switch back to torque
mode when the speed regulator output becomes less than the torque reference.

Sum

Configuring the drive in this mode enables an external torque input to be
summed with the torque command generated by the speed regulator. This mode
requires both a speed reference and a torque reference to be linked. This mode
can be used for applications that have precise speed changes with critical time
constraints. If the torque requirement and timing is known for a given speed
change, then the external torque input can be used to preload the integrator. The
timing of the speed change and the application of an external torque command
change must be coordinated for this mode to be useful. The “Sum Spd/Trq”
mode will then work as a feed forward to the torque regulator.

+

P314 [SLAT Err Stpt]

P315 [SLAT Dwell Time]

Low Pass

Filter

Speed Error > 0

Off

On

Speed Error < SLAT Setpoint

for SLAT Time

FSM State Controller

Application Dependant

Speed Reference Bias

Motor Speed Feedback

External Torque

Reference (ETR)

Speed Error

Speed Regulator

Output (SRO)

Forced Speed

Mode (FSM)

FSM - On

Off

PI

Regulator

M

ax

Select

Internal Torque
Reference (ITR)