Configuring the safe speed functions – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 350

Advertising
background image

350

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 6

Integrated Motion on the EtherNet/IP Network Applications for PowerFlex 755 AC Drives

Safe Speed Monitor Option
Module (20-750-S1)
Configuration

When a PowerFlex 755 drive is configured for Integrated Motion on the
EtherNet/IP Network the configuration of the Safe Speed Monitor functions are
accomplished via a web page.

Configuring the Safe Speed Functions

The Safe Speed Monitor module web page differs from the Embedded EtherNet/
IP adapter (port 13) web page that is enabled by setting adapter parameter P52
[Web Enable] to 1 “Enabled.” The Safe Speed Monitor module web page is not
accessible until the drive has established a network connection to a Logix
processor and the Integrated Motion on the EtherNet/IP Network connection
has been established. The web page is then accessed by entering the IP address of
the drive into a web browser (for example, http://192.168.1.20/). Currently,
safety configuration settings cannot be saved in the drive or downloaded to other
drives.