Duty Cycle for the Motor Overload

When the motor is cold, this function enables 3 minutes at 150%. When the
motor is hot, it enables 1 minute at 150%. A continuous load of 102% is allowed
to avoid nuisance faults. The duty cycle of the motor overload is defined as
follows. If operating continuous at 100% FLA, and the load increases to 150%
FLA for 59 seconds and then returns to 100% FLA, the load must remain at
100% FLA for 20 minutes to reach steady state.

Charging Overload Hz

Co

nt

in

uous R

atin

g

OL % = 10

OL % = 25

OL % = 50

150%

100%

20 Minutes

1 Minute

1 Minute