Sensorless vector – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 229

Advertising
background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

229

Motor Control

Chapter 4

1 = “Fan/Pump”
When this option is chosen, the relationship is 1/x2. Therefore, at full frequency,
full voltage is supplied. At 1/2 rated frequency, 1/4 voltage is applied. This
pattern closely matches the torque requirement of a variable torque load
(centrifugal fan or pump – load increases as speed increases) and offers the best
energy savings for these applications.

Sensorless Vector

Sensorless Vector mode uses a V/Hz core enhanced by excellent current
resolution, a slip estimator, a high performance current limiter and the vector
algorithms. The basic functions for SV are similar for all three motor types,
induction motor, permanent magnet motor, and synchronous reluctance motor,
however PM and SyncRel SV do not require Slip Frequency adjustments.

IM Sensorless Vector

Maximum Voltage

Base Voltage

(Nameplate)

Run Boost

Break Frequency

(Nameplate)

Maximum
Frequency

+

+

Elec. Freq.

V Ref.

Gate

Signals

V/Hz

Voltage

Control

Inverter

Motor

Current

Limit

Freq. Ref.

Speed Freq.

Current

Resolver

Current Feedback

Current Feedback - Total

Torque 1 Est.

Vector

Control

V Vector

Slip

Estimator

Torque 1 Est.

To

rq

ue

1

Es

t.

V/Hz Control

Slip Frequency

Advertising
This manual is related to the following products: