Pid output select, Pid configuration, Pid preload – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 79

Advertising
background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

79

Drive Configuration

Chapter 1

PID Output Select

Parameter 1079 [PID Output Sel]

“Not Used” (0) - PID output is not applied to any speed reference.

“Speed Excl” (1) - PID output is the only reference applied to the speed
reference.

“Speed Trim” (2) - PID output is applied to speed reference as a trim value.
(Default)

“Torque Excl” (3) - PID output is only reference applied to torque
reference.

“Torque Trim” (4) - PID output is applied to torque reference as a trim
value.

“Volt Excl” (5) - PID output is only reference applied to voltage reference.

“Volt Trim” (6) - PID output is applied to voltage reference as a trim value.

PID Configuration

Parameter 1065[PI Cfg] is a set of bits that select various modes of operation.
The value of this parameter can only be changed while the drive is stopped.

PID Preload

This feature steps the PID Output to a preload value for better dynamic response
when the PID Output is enabled. Refer to the diagram below. If PID is not
enabled, the PID Integrator can be initialized to the PID Preload Value or the
current value of the commanded speed. The operation of Preload is selected in
the PID Configuration parameter. By default, Preload Command is off and the
PID Load Value is zero, causing a zero to be loaded into the integrator when the
PID is disabled. As shown in Diagram A below, when the PID is enabled the PID
output starts from zero and regulates to the required level. When PID is enabled
with PID Load Value is set to a non-zero value the output begins with a step as
shown in Diagram B below. This can result in the PID reaching steady state

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Read-W

ri

te

Da

ta

T

yp

e

APPLIC

AT

ION

S

Pro

ces

s P

ID

1065

PID Cfg
PID Configuration

RW 16-bit

Integer

Main configuration of the Process PID controller.

Options

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Pe

rc

en

t R

ef

Ant

i W

in

dup

Stop

Mo

de

Fdbk Sqr

t

Ze

ro

C

la

m

p

Ramp Ref

Pre

lo

ad

In

t

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled