Rockwell Automation Publication 750-RM002B-EN-P - September 2013

191

Diagnostics and Protection

Chapter 3

to issue the actual fault at a higher current level or a slightly longer Shear Pin
time.

Other Points

The Shear Pin feature is not to be taken as a precise current reactionary feature.
There can be as much as +/- 5% error in the current feedback signal used to
determine shear point levels. Therefore it could be possible that the timer trip
point is being set and reset until the entire current reference is above a setpoint.

Shear Pin - Alarm then Fault

P7 [Output Current]

P436 [Shear Pin1 Level]

P439 [Shear Pin2 Level]

Motor Speed

Shear Pin 1
Time

Load Changes

Drive Faults

P952 [Fault Status A]

P959 [Alarm Status A]

P3 [Mtr Vel Fdbk]

Shear Pin 2 Time

Alarm
Indication

Alarm
Indication

Fault
Indication