Speed reference, For mor – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 251

Advertising
background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

251

Motor Control

Chapter 4

Speed Reference

The speed reference can come from a variety of sources. Some can be selected
through digital inputs or via bit manipulation of the Network Logic Command
Word:

HIM (local or remote)

Analog Input

Preset Speed Parameters

Jog Speed Parameters

Auxiliary Velocity Feedback

Network Communication

Process PID Loop

MOP Reference

DeviceLogix software

Figure 28 - PowerFlex 753 Speed Reference Selection Overview

Refer to the PowerFlex 750-Series Programming Manual, publication

750-

PM001

, Appendix A for more details on the PowerFlex 753 Control Block

Diagrams.

+

Spd Ref A

Trim Ref A

Trim % Ref A

Ref A

Auto

+

Spd Ref B

Trim Ref B

Trim % Ref B

Ref B

Auto

+

ENet Spd Ref

DPI Ports 1-6 Manual

Spd Ref

Command

Limit

Selected Spd Ref

Skip

Bands

Limited

Spd Ref

Direction

Mode

Vel Ref

Filter

x

Speed

Comp

Pos Reg

Output

Filter

Speed Ref

Scale

From

Position

Regulator

Limit

Velocity Reg

Ref

Motor Spd Ref

From

PI Regulator

(Trim Mode)

From

PI Regulator

(Exclusive Mode)

Jogging/

Oil Pump/
Autotune/

Homing/

Overrides

VF or SV

Droop

From

Slip Comp

Frequency

Ref

Limit

From

Velocity Trim

Regulator

Max Speed +

Overspeed Limit

From

PI Regulator

(Trim Mode)

Flux

Vector

Limit

Max Speed

Max Speeds

Speed Reference Selection

Speed Reference Control

Ramped

Vel Ref

Limit

Switch

Control

Speed Ref

Stop

Vector Ramp S-Curve

Linear

Ramp &
S Curve

V/F Ramp S-Curve

Linear

Ramp &
S Curve

Vector Speed Control

V/F Speed Control

Rate

Select

Speed
Status

Speed Feedback

Vector Ramp Status

F/F Ramp Status

Status

Ramped

Speed Ref

Presets 3-7 Auto

From

Pt-Pt Profile

Generator

Fiber

App.

Advertising