The bus voltage regulation setpoint is determined from bus memory (a means to
average DC bus over a period of time). The following tables and figure describe
the operation.

Option 0 “Disabled”

If [Bus Reg Mode

n] is set to 0 “Disabled” The Voltage Regulator is off and the

DB transistor is disabled. Energy returning to the DC bus increases the voltage
unchecked and trips the drive on over voltage once the voltage threshold is
reached.

Figure 2 -

PowerFlex 750-Series Bus Regulation – Disabled

Voltage Class

DC Bus Memory

DB On Setpoint

DB Off Setpoint

480

<685V DC

750V DC

On - 8V DC

>685V DC

Memory + 65V DC

320

360

460

484

528

576

453

509

650

685

750

815

880

DB Turn On

DB Turn Off

AC Volts

DC V

ol

ts

Bu

s R

eg

Cur

ve

#1

Bu

s R

eg

Cur

ve

#2

Bu

s M

em

ory

900

800

700

600

500

400

300

200

100

0

12

10

8

6

4

2

0

-0.2 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6

DC Bus Voltage

Speed Feedback

Over Voltage Trip Point

Stop Pressed

Motor Coasts

Seconds

DC Bu

s

Vo

lt

s

10

V

olt

s = Base Spee

d