Individual tests – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 38

Advertising
background image

38

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 1

Drive Configuration

Individual Tests

Some of the following tests are executed during an Autotune.

Resistance Test

This test is a Static test whether Static or Rotate is selected. Used to measure
Stator resistance.

Inductance Tests

This test is a Static test whether Static or Rotate is selected. One test is used for
Induction motors and a another is used for PM motors. The result from the
Induction test is placed into the Ixo parameter and the PM test is placed into the
IXd and IXq parameters.

Flux Test

This test is a Rotate test that measures the current under a no load condition. The
results are used for the flux current. If a Static test is used, the resulting value is
from a lookup table.

Slip Test

This test is a Rotate test that measures the difference between the rotor speed and
the stator speed. This measurement is taken during acceleration.

PM Offset Test

This test can create a small amount of motor movement so it needs to be
performed with the Rotate selection. The test reads the encoder position when
the drive outputs zero hertz.

Inertia Test

This test is a stand alone test that is used to measure the system inertia.

The drive sets this value in P76 [Total Inertia] as seconds of inertia. This reflects
the time it takes to accelerate the load at 100% torque to base speed. This
information can be very useful in determining the total inertia (in lb•ft

2

) that is

connected to a motor shaft.

Using the following formula,

and rearranging it to

Tacc

WK

2

ΔN

×

308 t

( )

-------------------------

=

WK

2

Tacc

308

t

( )

Ч

Ч

ΔN

--------------------------------------

=