Configuration – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 131

Advertising
background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

131

Feedback and I/O

Chapter 2

Catalog number 20-750-2263C-1R2T provides one transistor output and two
relay outputs on TB2 at the front of option module.

Refer to the PowerFlex 750-Series AC Drives Installation Instructions,
publication

750-IN001

, for PowerFlex 750-Series Option Module I/O wiring

examples.

Configuration

Each digital output can be programmed to change state based on one of many
different conditions. These conditions can fall into different categories.

Drive status conditions (fault, alarm, and reverse).

Level conditions (DC bus voltage, current, and frequency)

Controlled by a digital input.

Controlled by the network.

Controlled by DeviceLogix software.

Terminal

Name

Description

Rating

R0NC

Relay 0 N.C.

Output Relay 0 normally closed
contact

240V AC, 24V DC, 2A max
Resistive Only

R0C

Relay 0 Common
Output

Relay 0 common

R0NO

Relay 0 N.O.

Output Relay 0 normally open contact 240V AC, 24V DC, 2A max

General Purpose (Inductive) / Resistive

T0

Transistor Output 0 Transistor Output

24VDC = 1A max
24VDC = 0.4 Max for U.L. applications.
Resistive

TC Transistor

Output

Common

Transistor Output Common

T1

Transistor Output 1 Transistor Output

24VDC = 1A max 24VDC = 0.4 Max for
U.L. applications. Resistive