Sleep/Wake Sources

The P351 [SleepWake RefSel] signal source for the sleep/wake function can be
any analog input, whether it is being used for another function or not, a
DeviceLogix software source (P90 [DLX Real OutSP1] thru P97 [DLX Real
OutSP8]), or a valid numeric edit configuration. Configuring the sleep/wake
source is done through P351 [SleepWake RefSel].

Also, [Anlg In

n Hi] and [Anlg Inn Lo] parameters have no effect on the function,

however, the factory calibrated result, [Anlg In

n Value] parameter, is used. In

addition, the absolute value of the calibrated result is used, thus making the
function useful for bipolar direction applications.

The analog in loss function, configured by the [Anlg In

n LssActn] parameter, is

unaffected and therefore operational with the sleep/wake function, but not tied
to the sleep or wake levels and is triggered off the [Anlg In

n Raw Value]

parameter.

Refer to the PowerFlex 750-Series Programming Manual, publication

750-

PM001

, for more details.