Flying Start - Sweep Mode

This plot shows a coasting motor. When a start is commanded, the output
frequency jumps up to P520 [Max Fwd Speed]+ P524 [Overspeed Limit] at
some current. As the sweep frequency decreases the current is monitored. When
the sweep frequency matches the frequency of the coasting motor, the current
reverses and detection is complete. The motor is accelerated back to commanded
speed.

PowerFlex 753 Flying Start - Sweep Mode - Decelerating Load

Coasting Motor

Frequency Sweep

Start Pressed

Detection

Slope determined by P359

Frequency

Speed

Current