Rockwell Automation Publication 750-RM002B-EN-P - September 2013

77

Drive Configuration

Chapter 1

When the PID is disabled the commanded speed is the ramped speed reference.

When the PID is enabled the output of the PID Controller is added to the
ramped speed reference.

Exclusive Mode

In this mode, the output of PID regulator is the speed reference, and does not
“trim” a master speed reference. This mode is appropriate when speed is
unimportant and the only thing that matters is satisfying the control loop. In the
pumping application example below, the reference or setpoint is the required
pressure in the system. The input from the transducer is the PID feedback and
changes as the pressure changes. The drive output frequency is then increased or
decreased as needed to maintain system pressure regardless of flow changes. With

+

+

+

+

Slip Adder

Spd Ref

PID Ref

PID Fbk

Process PID

Controller

PID Disabled

Speed Control

Linear Ramp

and S Curve

Spd Cmd

Slip

Comp

Open

Loop

Process

PID

+

+

+

+

Slip Adder

Spd Ref

PID Ref

PID Fbk

Process PID

Controller

PID Enabled

Speed Control

Linear Ramp

and S Curve

Spd Cmd

Slip

Comp

Open

Loop

Process

PID