Rockwell Automation Publication 750-RM002B-EN-P - September 2013

71

Drive Configuration

Chapter 1

Ownership Example

The operator presses the HIM Stop button to stop the drive. When the operator
attempts to restart the drive by pressing the HIM Start button, the drive does not
restart. The operator needs to determine why the drive will not restart. The
operator first views the Start Owner to see if the HIM is issuing a valid Start.
When the start button on the HIM is pressed, a valid start is being issued as
shown below.

Because the start command is not maintained causing the drive to run, the
operator views the Stop Owner. Note that the status bar on the HIM indicates
that a stop has been asserted, but it does not indicate from which port the stop
command is originating. Notice that bit 0 is a value of “1,” indicating that the
Stop device wired to the Digital Input terminal block is open, issuing a Stop
command to the drive. Until this device is closed, a permanent Start Inhibit
condition exists and the drive will not restart.

Stop Asserted

0.00 Hz

AUTO

Port 00 Dev Param

Start Owner

x00x xxxx x000 0010

Bit 01 Port 1

ESC

920

F

PAR#

Stop Asserted

0.00 Hz

AUTO

Port 00 Dev Param

Stop Owner

x00x xxxx x000 0001

Bit 00 Digital In

ESC

919

F

PAR#