Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 4

Motor Control

Sel] and P680 [Trq Ref B Sel], the output can be summed together and along
with the output of “Torque Trim,” to become P4 [Commanded Trq].

Figure 31 - Torque Control - Reference Scale and Trim

For additional and expanded illustration of the Torque Control, refer to the
PowerFlex 755 Control Block Diagrams starting on

page 375

.

The following are key parameters related to the Torque Reference control
illustrated in

Figure 30

and

Figure 31

.

P313 [Actv SpTqPs Mode]

- Active Speed Torque Position Mode

Displays the Speed, Torque, Position Mode that is active, based on the dynamic
selection of modes A, B, C, and D, per P309…P312 [SpdTrqPsn Mode

n], and

digital input conditions programmed via P181 [DI SpTqPs Sel 0] and P182 [DI
SpTqPs Sel 1]. In some cases, such as operation in the SLAT min/max modes, the
final regulation mode may be forced into Speed Regulation. Refer to the Speed,
Torque, and Position mode bits in P935 [Drive Status 1] that indicate the active
regulation mode of the drive when it is running.

P675 [Trq Ref A Sel]

and P680 [Trq Ref B Sel] - Torque Reference A, B Select

Selects the source for a torque reference, used when the drive is configured to
command torque according to P309…312 [SpdTrqPsn Mode

n]. The values of

the torque reference sources are added together to provide a single torque
reference.

P676 [Trq Ref A Stpt]

and P681 [Trq Ref B Stpt] - Torque Reference A, B

Setpoint

x

679

Trq Ref A Mult

+

( Analog In 1 )

675

Trq Ref A Sel

( Analog In 2 )

From DIO Option Card

( Disabled )

Trq Ref A Stpt

( Setpoint )

676

x

684

Trq Ref B Mult

3,4

Other

0

1093

1079

PID Output Sel

PID Output Meter

(PID Torque Trim)

Other

0

3

Other

0

3

3 = Torque Excl
4 = Torque Trim

0.0

From DIO Option Card

Trq Ref B Stpt

4

Commanded

Trq

Default

677

Trq RefA AnlgHi

678

Trq RefA AnlgLo

*

Parameter

Selection

To Torq Ctrl,
Process Ctrl

1

195

DI Torque StptA

Bit

Source

Parameter

Selection

Default

( Analog In 1 )

680

Trq Ref B Sel

( Analog In 2 )

From DIO Option Card

( Disabled )

0.0

From DIO Option Card

682

Trq RefB AnlgHi

683

Trq RefB AnlgLo

*

( Setpoint )

681

0

Default

Parameter

Selection

* Note: Analog Hi, Lo
scaling only used when
Analog Input is selected