Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 4

Motor Control

Parameters

Applications

This function is usually associated with applications that require extended
acceleration times. Out of the box, the drive is set to “Automatic” and attempts to
get full motor stator flux based on motor nameplate information. In some cases
the loading and ramp curve during acceleration could have an adverse affect on
the drive's thermal manager. Some applications include mining conveyors or large
centrifuges. This function gives you the ability to manually be sure the motor
stator is fully fluxed up before acceleration by manually assigning a flux up time. It
can produce a better acceleration at low frequencies without excessive current.

High Resolution Feedback

The Universal Feedback option module, PowerFlex 755 drives only, interpolates
any sine/cosine signal into 1,048,576 counts per revolution.

The interpolation cannot be changed. It is 1,048,576 counts per revolution
regardless of the native cycles per revolution of the sine/cosine. Interpolation is
modified to 24 bits when P8 [FB0 Cfg] or P38 [FB1 Cfg] Bit 1 “24-bit Resol” is
set.

An acceptable sine/cosine signal is a 1 volt peak-to-peak voltage with a 2.5 volt
offset. Most feedback manufactures Sick (SSI), Stegmann (Hiperface), and
Heidenhain (En Dat, non en dat) meet this requirement.

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

MOT

O

R CONTROL

Mt

r Ctr

l O

pti

on

s

43

Flux Up Enable
Flux Up Enable
“Manual” (0) – Flux is established for P44 [Flux Up Time] before initial acceleration.
“Automatic” (1) – Flux is established for a calculated time period based on motor
nameplate data before acceleration. P44 [Flux Up Time] is not used.

Default:
Options:

1 = “Automatic”
0 = “Manual”
1 = “Automatic”

RW 32-bit

Integer

44

Flux Up Time
Flux Up Time
The amount of time the drive will use to try to achieve full motor stator flux. When a
Start command is issued, DC current at P26 [Motor NP Amps] level is used to build stator
flux before accelerating.

Units:
Default:
Min/Max:

Secs
0.0000
0.0000 / 5.0000

RW Real