Rockwell Automation Publication 750-RM002B-EN-P - September 2013

255

Motor Control

Chapter 4

Jog

When the drive is not running, pressing the HIM’s Jog soft button or a
programmed Jog digital input function or by Logic Command (sent over a
communication network) causes the drive to jog at a separately programmed jog
reference. This jog speed reference value is entered in P556 [ Jog Speed 1] or P557
[ Jog Speed 2].

Scaling of an Analog Speed Reference

Refer to

Analog Inputs on page 105

.

Polarity

The polarity configuration can be selected as unipolar, bipolar, or reverse
disabled via P308 [Direction Mode]. When in Unipolar mode, the sign of the
speed reference value (and therefore direction of motor rotation) is determined
by P879 [Drive Logic Rslt] Bit 4 “Forward” and Bit 5 “Reverse.” When in Bipolar
mode, the sign of the speed reference value determines the direction of motor
rotation. When in Reverse Disable mode, negative speed reference values are
rejected and a zero speed value is used in their place.

935

17

0

1,0

556

557

0,1

1

879

2 19

Jogging

Drive Status 1

(Jogging)

Jog1
Jog2

Jog Speed 1

Jog Speed 2

Drive Logic Rslt

2

X

1

1

0

0

308

0

(+1)

(-1)

Direction Mode Control

Direction Mode

Max

Forward

Command Logic

Unipol

Fwd

Unipol

Rev

Unipolar

Rev Disable

Bipolar