Connect to the GuardPLC Controller 1-5

Go Online with the
GuardPLC Controller

The following flowchart illustrates the steps required to successfully
go online with the GuardPLC controller.

The steps are described in detail in the following sections.

Step 1: Open RSLogix

Guard PLUS!

Do you already know

settings?

Is the

FAULT LED

illuminated?

Do you

think you know the

controller settings?

Did

communication

settings read IP/SRS

successfully?

Do you

want to change these

settings in the

controller?

Is the

controller in RUN

mode?

Ping successful?

Are you online with

the correct settings?

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

Step 2: Create a New

Project

Step 3: Configure the

controller type and SRS

Step 12: Fault Recovery

after Reset.

Step 4: Communication

Settings

Step 8: Change

Controller Mode to

STOP

Step 9: Reset Controller

Default Settings

(2)

Step 6: Move Settings

into Offline Project

Step 7: Connect to

Controller Using

Control Panel

Step 5: Change

Settings via MAC

Address

Step 10: Ping the

Controller

Step 11: Configure

Controller IP

Address

(1)

Notes:

(1) Assume correct SRS was entered in Step 3.

(2) The controller reverts back to its prior settings if it is
not re-configured before the next power cycle.

(3) If the controller was previously running and the SRS
was changed in Step 5, or if the controller is new
(out-of-box), the only way to clear the FAULT is to
download a program with a matching SRS.

DONE

(3)

Note: This path is not possible for
GuardPLC 1200 and GuardPLC 2000
controllers.