Publication 1753-PM001A-EN-P - November 2005

1-14 Connect to the GuardPLC Controller

Step 8: Change the Controller to STOP Mode

To change the controller to STOP mode, choose Resource>Stop from
the Control Panel or use the Stop icon.

When in STOP Mode, the Control Panel appears as follows:

Close the Control Panel.

Step 9: Reset the Controller to the Default Settings

In some cases, you may have to reset the GuardPLC controller to its
default IP address and SRS.

GuardPLC 1600 and 1800 controllers have a Reset button that is
accessible via a small hole directly to the right of the Ethernet ports on
top of the controller. The Reset button returns the IP address, SRS and
Password settings to:

Parameter

Setting

IP Address

192.168.0.99

SRS

60000

Username

Administrator

Password

[none]