Create a function block program, Create a function block program -13 – Rockwell Automation 1753-PCS-PAR Using RSLogix Guard PLUS! with GuardPLC Controllers User Manual

Page 53

Advertising
background image

Publication 1753-PM001A-EN-P - November 2005

Create a GuardPLC Project 3-13

4. Select the Input tab on the Connect Signals dialog.

5. Connect the Count signal you created to the Counter Value

input.

These signals can now be used in your application program logic.

Create a Function Block
Program

The following example creates code to start and stop a motor using
the two input signals we created earlier.

Counter[xx] Output Variable

Description

5/24V Mode

True (1) = 24V
False (0) = 5V

Auto Advance Sense

True (1) = Count Up or Down Based on Direction
False (0) = Count Up Regardless of Direction

Direction

If Auto Advance Sense is False (0), then count in the
indicated Direction:

• True (1) = Down
• False (0) = Up

Gray Code

True (1) = Use Gray Code Mode
False (0) = Use Pulse Mode

Reset

True (1) = No Counter Reset
False (0) = Reset Counter

Count Up regardless of Direction

Count Up based on Direction

TIP

For more information on Function Block
programming, consult the online Help and
Chapter 8, Create User-Defined Function Blocks.

Advertising