Publication 1753-PM001A-EN-P - November 2005

1-20 Connect to the GuardPLC Controller

Login Dialog

The Login dialog defines the communication parameters between the
controller and the programming terminal.

Field

Description

IP address

The IP address of the controller on the Ethernet network.

The factory-set IP address is 192.168.0.99.

SRS

SRS stands for System, Rack, Slot. The rack and slot IDs are already preset by the controller, so you only
need to enter the system ID. You can enter any number from 1 to 65,535. However, the number must be
unique from the programming terminal and from any other GuardPLC controllers on the same
Peer-to-Peer Ethernet.

The default (factory-set) SRS is 60000.

Username

(default = Administrator)

Your username.

The Administrator assigns a username. The username is sensitive to upper and lower case characters. A
username can only contain letters, numbers, and underscore characters.
You can define as many as 10 usernames per GuardPLC controller.

Password

(default = <blank>)

Your password.

An Administrator assigns a password. The password is case sensitive. A password can only contain
letters, numbers, and underscore characters.

Access Type

Your access level.

Login as one of these options:

Administrator

highest privileges
manage usernames and passwords
read data from controller
write routines and data into controller
force tags
stop, start, freeze, and force a routine
download an operating system
change IP address and system ID
reboot the controller
can also login under read/write and read levels

Read/Write

read data from controller
write routines and data into controller
force tags
start, stop, freeze, and force a routine
can also login under read level

Read

lowest privileges
only read data from controller

As many as five users can login to the same controller at the same time; however, only one of those
users can login as Administrator or Read/Write. The others must login with Read access. If you login
while someone else is logged in with Administrator or Read/Write access, you automatically get Read
access, regardless of the access type you select.

For new controllers, and if the backup battery was removed from a GuardPLC 1200 or 2000 controller,
access is available using the following system defaults:
Username:

Administrator

Password

<blank>

Access Type

Administrator