Monitor and Force Signals 5-5

Specify Force Values and
Force Marks

To set a signal with a force value, you:

1. Enter the force value for the signal in the Force column.

2. Double-click in the F column to mark that you want the

controller to use the force value rather than the process value.

3. Send the force value(s) to the controller.

The Force Editor displays the force value(s) in the R-Force
column. A mark in the RF (resource force) column indicates that
the controller will use the corresponding force value instead of
the process value when forcing is enabled.

Multiple force values can be written into the controller at the same
time. The force values remain saved in the controller until the routine
is reloaded. If the routine is stopped, the resource force marks are also
reset.

TIP

For Boolean signals, True or False and
1 or 0 are acceptable values.