Publication 1753-PM001A-EN-P - November 2005

1-18 Connect to the GuardPLC Controller

To recover from this fault:

1. Choose Extra>Change System ID from the Control Panel.

2. Verify that 60000 appears in the first window with 0 in the

second, as shown below.

3. Click OK.

The Fault LED should turn off, and the Control Panel should show
that the CPU State has changed to STOP/VALID CONFIGURATION, as
shown below.

TIP

The Online indicator is white because the GuardPLC
controller is in STOP/VALID mode.