A-2 Specifications

Electrical/EMC

Emissions

CISPR 11: Group 1, Class A

ESD Immunity

IEC 61000-4-2:

• 6 kV contact discharges
• 8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

• 10V/m with 1 kHz sine-wave 80% AM from 30 MHz

to 2000 MHz

• 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
• 10V/m with 200 MHz 50% Pulse 100% AM at 1890

MHz

• 3V/m with 1 kHZ sine-wave 80% AM from 2000 MHz

to 2700 MHz

EFT/B immunity

IEC 61000-4-4:

• ±2 kV at 5 kHz on power ports
• ±2 kV at 5 kHz on communications ports

Surge Transient
Immunity

IEC 61000-4-5:

• ±1 kV line-line (DM) and ±2 kV line-earth (CM) on

power ports

• ±2 kV line-earth (CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:

• 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz

to 80 MHz