10-2 Monitor Status

Alphanumeric Display

At Power Up

When you apply power to the 1753-DNSI safety scanner, check the
scanner’s alphanumeric display to determine if the module is
operating properly. It displays the following:

• firmware revision
• MAC ID
• DeviceNet communication rate

During Operation

Following power up, the alphanumeric display on the safety scanner
displays the following information:

HSP
Status

Off

The module has not received any messages on the serial
interface.

Green, On

The module is transmitting data over the serial
communication interface.

Green, Flashing

The serial interface is ready for communication, but the
controller is sending messages that do not match the
safety scanner’s current configuration.

Red, Flashing

The connection to the controller was lost after being
established at least once since power up.

LED

Color/State

Description

Display

Description

A#xx

‘xx’ is the MAC ID of the scanner. A status string follows.

IDLE

The scanner is in idle mode.

RUN

The scanner is in run mode.

Duplicate
Node Failure

The address of the scanner is already in use by another device on the network. Change the
address to an unused address.